Haier Expert Air Conditioning System
Haier’s Expert series is a single-split wall mounted air conditioning series designed for user comfort and energy efficiency. Also compatible with multi-split and light commercial systems.
A number of comfort and cleaning features are included as standard.
- Simple pairing with hOn wi-fi app for control over unit output and basic functions
- Energy rating of A+++/A++
- Two sterilisation technologies: UVC rays and ion plasma generator
- Dual eco sensor adjusts air flow towards or away from those in the room and activates power saving mode when the room is empty
- iFeel function detects the room temperature from the remote control and sends the information back to the indoor unit every 3 minutes
A...
Просмотров: 71

Видео

Haier Revive Plus Air Conditioning System
Просмотров 1432 месяца назад
Haier’s budget friendly Revive Plus series is a single-split wall mounted air conditioning series designed for user comfort and energy efficiency. Also available as a multi-split unit. A number of comfort and cleaning features are included as standard. - Simple pairing with hOn wi-fi app for control over unit output and basic functions. - Energy rating of A - 3 different energy-saving eco modes...
Haier Revive Air Conditioning System
Просмотров 2317 месяцев назад
Haier’s budget friendly Revive series is a single-split wall mounted air conditioning series that pioneers the new Coanda Plus, to further boost the range of circulation at a smoother air flow. Each unit is fitted with a self-cleaning system, and has smaller dimensions for ease of installation. A number of comfort and cleaning features are included as standard. - Integration into the hOn wi-fi ...
Hitachi Centrifugal Hidden VRF Air Conditioning System
Просмотров 392Год назад
Hitachi's centrifugal VRF system is unusual because the ducted condensing unit is completely hidden inside the building, either in a false ceiling or concealed behind the facade. This makes it an ideal choice for city centre locations where there's no access to a suitable space for a traditional condensing unit. It is also an attractive option for listed buildings and conservation areas where p...
CO2 (R744) Refrigeration for Riverford Organics | Panasonic & LU-VE
Просмотров 1,1 тыс.2 года назад
In this project, Keep It Cool Refrigeration installed a 36kW CO2 system in a butchery for Riverford Organic Farmers in Devon. Four 10HP condensing units from Panasonic will supply three new cold rooms. With a focus on energy-saving, the project includes evaporators with EC fans from LU-VE as well as EEVs and MPXPRO controllers from CAREL. By switching to R744, this project could reduce monthly ...
LG Dual Vane Air Conditioning Cassettes
Просмотров 812 года назад
The latest cassette units from LG have two individual vanes to deliver a wider airflow. Air flow can be customised using different modes for indirect airflow, up and down swing, direct airflow and power mode to suit the room type. LG Dual Vane is available with a 5-step filtration air purification system for improved air quality. It can also be monitored and controlled by mobile devices using L...
Mini-VRF Heat Recovery Installation Using LG Multi V S | Royal Free Hospital
Просмотров 1,2 тыс.2 года назад
In this video case study, we join Aircool Systems, an air conditioning contractor based in Kent, as they commission a new LG heat recovery system in a refurbished research facility at the Royal Free Hospital in North West London. The LG Multi V S system is a single-phase 3 pipe mini-VRF, which on this project will provide independent heating and cooling for three rooms. The 6HP outdoor unit con...
World Refrigeration Day 2021 : Cool Careers
Просмотров 7453 года назад
A member of our internal sales team, Neil Cooper has just completed the first year of his NVQ level 2 in refrigeration and air conditioning at Eastleigh College. For World Refrigeration Day 2021, we asked him to introduce us to some of his classmates to understand what apprenticeships mean to them in the HVACR industry. #coolingchampions #wrefd21 #coolcareers #worldrefrigerationday For more abo...
Haier Flexis R32 Air Conditioning Range
Просмотров 1393 года назад
Available in two stylish options (Matt White or Matt Black), Haier’s Flexis Plus R32 range achieves A cooling efficiency and A heating performance. It features an energy-saving double-motion eco-sensor detects movement of people, level of activity and intensity of daylight to automatically adjust cooling. It is also ultra-quiet with a DC inverter fan, air ducts and motor optimised to keep noise...
Haier's Pearl AC Range | with UVc Sterilisation
Просмотров 1,6 тыс.3 года назад
Available as a 2.6, 3.2 or 5kW single split system, the Pearl range from Haier features UVc sterilisation, defrost self-cleaning, high temperature elimination of bacteria and viruses and easy installation. Independent tests by Texcell, a gobal contract research organisation, demonstrate that the UVc light generator is effective in inhibiting Covid-19 virus with up to 99.998% efficiency (within ...
Haier HVAC Research & Development
Просмотров 1563 года назад
Based in Qingdao, China, Haier's futuristic air conditioning R&D facility has more than 150 laboratories. It performs tests for sun, snow, rain, sand and humidity - and boasts the world’s tallest ‘drop tower’ used for testing long refrigerant piping. For more information about Haier in the UK, visit www.hawco.co.uk/haier or contact our expert sales team on 01483 869 070 or email sales@hawco.co.uk
Monobloc Air to Water Heat Pump Installation - Using LG's Therma V
Просмотров 91 тыс.3 года назад
In this video case study, we ask Greg Walker of GDI Cooling, an air conditioning and refrigeration company in Oxfordshire, to explain why they recommended an LG Therma V monobloc air source heat pump to replace an outdated oil boiler for one of their residential customers. He explains how the air to water heat pump saves space, is easy to install and integrate with the existing hot water tank a...
Cold Room Installation in a Private Home - Using Embraco's Bioma Condensing Unit
Просмотров 1,8 тыс.4 года назад
We worked with Cold Control Services - an award-winning refrigeration contractor in Hampshire, UK - to supply the refrigeration equipment for a walk-in cold room in a prestigious London home. The application required a solution that was incredibly quiet, easy to maintain and looked good in a domestic setting. In this video, AJ Grant (Refrigeration Development Manager at Cold Control) shows us a...
Why Embraco's Bioma Condensing Unit is So Quiet
Просмотров 2,9 тыс.4 года назад
Designed for cold room projects, the Bioma condensing unit from Embraco features technologies to minimise fan noise and absorb sound and vibration. These include a unique sound baffle for better air flow management plus a lower fan speed, full acoustic jacket and robust construction. For more details, visit www.hawco.co.uk/bioma or contact our technical team on 01483 869 069 with any further qu...
Hitachi Frost Wash AC Cleaning System
Просмотров 6 тыс.5 лет назад
Every 200 hours, Hitachi air conditioners fitted with the innovative Frost Wash feature go through a unique cleaning cycle to clear bacteria, mould, dust and dirt from the heat exchanger. Dust is trapped by freezing moisture on the coil, which is then melted and washed away. Finally, the coil is dried leaving a clean and hygienic coil. Tests show that Frost Wash reduces the build up of bacteria...
Setting a Second Set Point: LAE AT2-5 Digital Controller
Просмотров 37 тыс.5 лет назад
Setting a Second Set Point: LAE AT2-5 Digital Controller
Fixing an E2 Probe Fault: LAE AT2-5 Digital Controller
Просмотров 71 тыс.5 лет назад
Fixing an E2 Probe Fault: LAE AT2-5 Digital Controller
Fixing An E1 Probe Fault: LAE AT2 5 Digital Controller
Просмотров 38 тыс.5 лет назад
Fixing An E1 Probe Fault: LAE AT2 5 Digital Controller
Setting A Light Control Switch: LAE AT2 5 Digital Controller
Просмотров 9 тыс.5 лет назад
Setting A Light Control Switch: LAE AT2 5 Digital Controller
Programming an LAE AT2-5 Digital Controller
Просмотров 150 тыс.5 лет назад
Programming an LAE AT2-5 Digital Controller
Setting a Deadband (Two-Stage) Control: LAE AC1-5 Digital Controller
Просмотров 7 тыс.5 лет назад
Setting a Deadband (Two-Stage) Control: LAE AC1-5 Digital Controller
Setting Relay for Refrigeration/Heating: LAE AC1-5 Digital Controller
Просмотров 6 тыс.5 лет назад
Setting Relay for Refrigeration/Heating: LAE AC1-5 Digital Controller
Setting On/Off Times (If Probe Fails): LAE AC1-5 Digital Controller
Просмотров 4,5 тыс.5 лет назад
Setting On/Off Times (If Probe Fails): LAE AC1-5 Digital Controller
Setting Min & Max Set Points: LAE AC1-5 Digital Controller
Просмотров 24 тыс.5 лет назад
Setting Min & Max Set Points: LAE AC1-5 Digital Controller
Add/Remove Decimal Point: LAE AC1-5 Digital Controller
Просмотров 3,6 тыс.5 лет назад
Add/Remove Decimal Point: LAE AC1-5 Digital Controller
Programming an LAE AC1-5 Digital Controller
Просмотров 30 тыс.5 лет назад
Programming an LAE AC1-5 Digital Controller
Fixing an Overrange ("or") Probe Fault: LAE AC1-5 Digital Controller
Просмотров 9 тыс.5 лет назад
Fixing an Overrange ("or") Probe Fault: LAE AC1-5 Digital Controller
Programming an LAE LTR-5 Digital Controller
Просмотров 38 тыс.5 лет назад
Programming an LAE LTR-5 Digital Controller
Fixing an E1 Probe Fault: Eliwell IDPlus 961 Digital Controller
Просмотров 101 тыс.5 лет назад
Fixing an E1 Probe Fault: Eliwell IDPlus 961 Digital Controller
Probe Settings: Eliwell IDPlus 961 Digital Controller
Просмотров 33 тыс.5 лет назад
Probe Settings: Eliwell IDPlus 961 Digital Controller

Комментарии

  • @rudy8662
    @rudy8662 3 года назад

    Great video Team.... Finally a simple explanation.... Can you guys do a similar video on the danfoss ERC range (213 ...214) thanks again

  • @muhammadkamran851
    @muhammadkamran851 3 года назад

    So helpful video, thank you dear!

  • @bruceboucher2134
    @bruceboucher2134 3 года назад

    Can we get some annual operating costs now Heat Pumps are being legislated soon

  • @bruceboucher2134
    @bruceboucher2134 3 года назад

    Hi Don't use the word refrigeration to the lay person, also use pre-insulated at the distance you are considering when putting the piping through to the home

  • @miodragnedic378
    @miodragnedic378 4 года назад

    Thanks a lot. Big help.

  • @calmandsmile2867
    @calmandsmile2867 4 года назад

    Good presentation. Thanks

  • @farooqahmad250
    @farooqahmad250 4 года назад

    Please make video ellwell902 E1

  • @lancewilliams3033
    @lancewilliams3033 4 года назад

    I have an LAE AH1-5. I'm not sure if it's the same for the AC1-5, but LAE has for some unknown reason deliberately removed the decimal point for temperatures above 19.9C, even when ScL = 1C The result is that the controller is unusable for the heating application I bought it for!

    • @HawcoCoUk
      @HawcoCoUk 4 года назад

      Hi Lance. Thanks for your comment. Our technical team have suggested the following: For the AH1-5 with SCL set to 1, the value displayed will show a decimal point between -9.9°C to 19.9°C. This means from -10°C to -50°C, there is no decimal point and from +20°C to +80°C there is also no decimal point. For a heating application that needs a decimal point, you would need a more accurate process controller. Usually for heating applications over 20°C, whole numbers - with no decimals - are sufficient. For the AC1-5 with SCL set to 1, then the decimal point is always there. However, ensure you use a thermocouple or a PT100 - as PTC/NTC probes have a tolerance themselves of approx.+/- 1°C. So if decimal points are needed then it must mean serious accuracy is required from the probe also.

    • @lancewilliams3033
      @lancewilliams3033 4 года назад

      @@HawcoCoUk Thanks for replying. It just seemed so random to have the decimal point for some of the range, but not the rest. I'm trying a Carel IR33 in PID mode now - will see how it goes.

  • @kadkadbrf627
    @kadkadbrf627 4 года назад

    can i control the heat win carel for eggs incubatore in 37 C plz answer me

    • @HawcoCoUk
      @HawcoCoUk 4 года назад

      Dear Kad Kadbrf Both the Carel Easy Cool and Carel Easy Freeze controllers are designed for refrigeration applications only. For a controller to be used at 37C, you would require a different kind of controller, such as the LAE AC1-5. Take a look at this video - ruclips.net/video/U17XnfOZsk4/видео.html - which explains more about the parameters of this controller - or visit our website for more details www.hawco.co.uk/en/refrigeration/controllers/lae/lae-panel-two-stage-thermostat The Hawco Team

    • @kadkadbrf627
      @kadkadbrf627 4 года назад

      @@HawcoCoUk thank you <3

  • @arifseikh7891
    @arifseikh7891 4 года назад

    Thank you sir i am very happy to know this cotroller thankyou so nuch from india

  • @jhosepherrera3463
    @jhosepherrera3463 4 года назад

    Por favor un video en español

  • @susyar8332
    @susyar8332 4 года назад

    hi how to changes to fahrenheit to Celsius

    • @HawcoCoUk
      @HawcoCoUk 4 года назад

      Hi Susy Ar The default setting on a Carel Easy Cool controller is set to Celsius. To change this to deg F, first push and hold the set button to go into the parameters. (The default password for Carel is 22) Then, use the up or down arrows to find the probe setting you need, which is parameter /5. Select option 0 for Celsius and select option 1 for Fahrenheit. Press the set button to save the changes. Be aware that this will only change the display from C to F. It will not convert the temperature readings from Celsius to Fahrenheit. So for example, 20°C will be displayed as 20°F (it will not convert the set point to 68°F). I hope this helps. The Hawco Team

    • @susyar8332
      @susyar8332 4 года назад

      Hawco thanks so much. I wanna trying 😉

  • @RaviYadav-nx7ft
    @RaviYadav-nx7ft 4 года назад

    dear friend why in my controller eco light is blinking.

    • @HawcoCoUk
      @HawcoCoUk 4 года назад

      Hi Ravi The flashing eco light shows that the economy setpoint has been activated. The economy setpoint is a different setpoint that can be initiated during times when the cabinet is not being used (for example at night when a store is closed) If you wanted to deactivate this setting, you will need to navigate to the CNF folder. The parameter H31 controls the function of the UP key while the parameter H32 controls the function of the DOWN key. Either one of these will be set to 3 (which means economy mode activation). Press this key to activate or deactive the economy setpoint mode. Please remember any changes to any parameter in the CNF folder will require you to power down the controller or the cabinet and switch back on to fully save the new parameters. Hope this helps. The Hawco Team

  • @FilmesLaranjeiro
    @FilmesLaranjeiro 4 года назад

    Hi Hawco. I was wandering is there a controller capable of defrosting triggered by evaporator temperature...I'm thinking water heating for radiant floor...

    • @HawcoCoUk
      @HawcoCoUk 4 года назад

      Hi Antonio It depends on the temperature you are hoping to achieve but you can set a LAE AT2-5 controller to switch off by either time or by temperature, whichever is reached first. For example, the two parameters you would need are: The DLI parameter which controls the defrost end temperature The DTO parameter which controls the maximum defrosting duration If you need any further advice on a specific application, email technical@hawco.co.uk and we will try to help you. The Hawco Team

  • @Belgacem-pe4ur
    @Belgacem-pe4ur 4 года назад

    Please pid

  • @leseur4821
    @leseur4821 4 года назад

    Informative thanks. Please discuss OSP setting in the CP folder and how it effects the setpoint. Thank you.

    • @HawcoCoUk
      @HawcoCoUk 4 года назад

      Thanks for your comment. The OSP parameter refers to the temperature value that should be added to the setpoint when using the economy function mode. You should engage and disengage the economy function mode manually through a pre-configured key or controller digital input. You can configure the down key to do this. In this case, you should set parameter H32 to “3”. After that, power the unit off/on via the isolator. Then the DOWN button can be used to manually turn off/on economy function mode. The same function can also be found with IDPlus 971 and IDPlus 974 controllers. Refer to the Eliwell instruction manual for the IDPlus range of controllers for full details - see bit.ly/2WlSuon. Details of OSP setting can be found on page 26 and the H32 parameter on page 29. Hope that helps. Get in touch with technical@hawco.co.uk if you need further advice.

    • @leseur4821
      @leseur4821 4 года назад

      @@HawcoCoUk Ok? I gather that from the manual but specifically how? If my setpoint (SET) is set at -19 Degrees C and I put in an OSP setpoint of +5 Degrees, how does it affect my E1 (enviroment probe) reading. Will the actual independant measured temp be -14 or -24?

    • @HawcoCoUk
      @HawcoCoUk 4 года назад

      For this scenario, the probe will look to increase the set point by 5 deg C. from -19C to -14C while economy function mode is active

    • @leseur4821
      @leseur4821 4 года назад

      @@HawcoCoUk Ok, now it makes sense. Thank you

  • @hollyvictoria2658
    @hollyvictoria2658 4 года назад

    I've got a medical fridge with this on it and it just don't understand how to make it colder

    • @HawcoCoUk
      @HawcoCoUk 4 года назад

      Hi Holly. Thanks for your question. With medical fridges, we always recommend that you go back to the fridge manufacturer for any help like this. Hope they are able to answer your question. The Hawco team

    • @hollyvictoria2658
      @hollyvictoria2658 4 года назад

      @@HawcoCoUk thankyou

  • @mohamedkamel1611
    @mohamedkamel1611 4 года назад

    How can set the thermostat at a temperature of 37.5 ...I can't set the temperature to a comma

    • @HawcoCoUk
      @HawcoCoUk 4 года назад

      Hi Mohamed The parameter you want is SCL. With SCL set to “2: This means that a decimal point is not present (ie “20 deg c”) With SCL set to “1”: This means that a decimal point is present. This now means that what was once “20 deg c is now 2.0 deg c” However, if you ever change the SCL parameter from “2” to “1” (or vice versa) please ensure you check all the parameters as they will all be affected - ie HYS (hysteresis) was “05 deg c” is now “0.5 deg c” automatically!! Hope that makes sense. The Hawco team

    • @mohamedkamel1611
      @mohamedkamel1611 4 года назад

      @@HawcoCoUk..Thank you very much for your reply- I understand that if I put HYS at 1.0 and SP at 38 ° C this might give me an average temperature of about 37.5 ° C

    • @HawcoCoUk
      @HawcoCoUk 4 года назад

      Dear Mohamed Setting HYS to “1.0” is too small a tolerance for the controller and probe to read unless you are using a K-type / J-type thermocouple. If you are using an NTC or PTC thermistor, you should increase HYS to at least “2.0”. Hope that helps. The Hawco team

  • @kamalolo8490
    @kamalolo8490 4 года назад

    Good

  • @aniskhaled8491
    @aniskhaled8491 4 года назад

    Ci può spiegare un sistema PID

    • @HawcoCoUk
      @HawcoCoUk 4 года назад

      Thanks for your suggestion. We will produce a video explaining a PID system when we record our next set of videos. In the meantime, here is a link to the manual for the LAE AC1-5 that contains information on setting PID parameters for this controller. www.hawco.co.uk/en/media/bluelogic/legacyproducts_uploadfiles/l/a/lae-ac1-5-controller-instructions_6.pdf If you need any help with a particular application, contact us at technical@hawco.co.uk and we will do our best to help you.

  • @syedsaad5781
    @syedsaad5781 4 года назад

    👍👌

  • @amoomere9548
    @amoomere9548 4 года назад

    Thank you

  • @liamp5
    @liamp5 4 года назад

    Excellent thankyou :)

  • @timmywilson1347
    @timmywilson1347 4 года назад

    What is one for in defrost modes???

    • @HawcoCoUk
      @HawcoCoUk 4 года назад

      Dear Timmy The defrost parameter (d0) allows you to choose the defrost type required, depending on whether an electric heater or the injection of hot gas is the method being employed. There are five options available, which are 0=heater; 1=hot gas; 2=heater by time; 3=hot gas by time and 4=heater by time with temperature control. You can download a technical leaflet about the Easy Freeze controller with all of the parameters on this page of the Carel website - www.careluk.com/product/easy-freeze If you have any further questions, contact us at technical@hawco.co.uk.

  • @DesiOutdoors
    @DesiOutdoors 5 лет назад

    Hi there , i have areneg chiller in my shop and carel controller was installed on it after the previous controller (dixell) stopped working ..now the problem is as the weather goes warm the bottom side of the chiller start frosting and the top side gets warmer ...no idea what is the problem , can you plz let me know setting for dairy and meat items .

    • @HawcoCoUk
      @HawcoCoUk 5 лет назад

      Could you confirm the model number of the Carel controller you are using. Then we can send the right instruction sheet to you which should help you with your issue. Thanks

    • @DesiOutdoors
      @DesiOutdoors 5 лет назад

      @@HawcoCoUk Hi , I can't see the model number but it says Easy Cool

    • @HawcoCoUk
      @HawcoCoUk 5 лет назад

      Carel use the model number PZD*SNP0E1 for their Easy Cool controller. Details of the controller can be found on their website here - bit.ly/32hN4e2 If you need to buy a replacement controller, they are available from the Hawco website at www.hawco.co.uk/en/carel-easy-cool-controller-for-normal Hope that helps.

    • @DesiOutdoors
      @DesiOutdoors 4 года назад

      @@HawcoCoUk Hi , can you plz make a video for how to program carel easy cool

  • @jamesbutler4979
    @jamesbutler4979 5 лет назад

    How would you go about setting this up on a beer chiller? Any advice would be great. Thanks

    • @HawcoCoUk
      @HawcoCoUk 5 лет назад

      Hi James The set point required should be between +8°C and +12°C, depending on the product (e.g. wine, beer, ale etc). Defrost cycles will be minimal as the evap temp will be above +1°C. The easiest way to set up your controller would be to start by applying one of the four standard defaults (AP1-AP2-AP3-AP4) which come with the Eliwell IDPlus 961.Then you can change the setpoint as required. The most suitable default application for a beer chiller is AP2. To find out how to load this default application, refer to page 14 of the IDPlus instruction manual which can be downloaded here - bit.ly/2WlSuon Then to adjust the setpoint to between +8°C and +12°C, refer to page 19 of the same instruction manual. A full description of the AP2 default parameters can be found on page 25. If you need any more advice, email technical@hawco.co.uk and we will do our best to help you.

    • @jamesbutler4979
      @jamesbutler4979 5 лет назад

      Top stuff thanks a lot for the reply

  • @samuelsamknx8597
    @samuelsamknx8597 5 лет назад

    This is very helpful. Thank you for sharing.

  • @payagph5107
    @payagph5107 5 лет назад

    Can you tell me the proper setting for a vegetable fridge?

    • @HawcoCoUk
      @HawcoCoUk 5 лет назад

      Thank you for your comment. Every application is different and there are a number of factors you need to consider to get the right setting for your particular situation. If you can send some more details about what you would like to achieve to technical@hawco.co.uk we would be happy to try to help you.

  • @diaahleihil8393
    @diaahleihil8393 5 лет назад

    to get the highest temp, should i do it as you did but the set point is the max ?

    • @HawcoCoUk
      @HawcoCoUk 5 лет назад

      Hi Diaa, Thanks for your question. To clarify, higher setpoint (SPH) and lower setpoint (SPL) is the range our target setpoint (1SP) can be selected between. It is good to set a higher and lower setpoint as it allows end users to change the setpoint (1SP) within the range or margin set up by the installer. If you need any more help, email us at technical@hawco.co.uk or call us +44 (0)1483 869 069